Find Voltage Switchgear, Low Voltage Switchgear, HV Switchgear on Industry Directory, Reliable Manufacturer/Supplier/Factory from China.

Inquiry Basket (0)
Home > Products > HV Switchgear > Outdoor AC Metal-Clad Switchgear (ZHW2-12)

Outdoor AC Metal-Clad Switchgear (ZHW2-12)

Basic Info

Model No.:  ZHW2-12

Product Description

Model NO.: ZHW2-12 Structure: Double-column Disconnector Frequency: 50Hz Trademark: VILLE Origin: China Type: High-voltage Installation: Outdoor High-voltage Rate Voltage: 12kv Specification: IEC Standard HS Code: 85 General:
ZHW2-12 Outdoor AC HV Metal-clad Ring Main Unit Switchgear (hereafter referred to as Outdoor Ring Main Unit) is suitable for Outdoor distribution network of cable incoming and outgoing line with AC 50Hz, 12 kV rated voltage. It is widely used in the industrial zone, residential area and commercial centers. As switchgear of RMU Power Supply or terminal power supply, it can break load current and break the short circuit current by fuse. It is specialized in the power grids free of maintenance and with high degree of automation. This outdoor Ring Main Unit has replaced the regular switching station and it cuts down the occupied area of outgoing cable largely and the cost as well as reducing the loss of the cable.

Product feature:
A. This product has two structures. One is that the outdoor RMU is mounted with vacuum load switch and load Circuit Breaker made by ourselves. It is resembled by weld and bent corrosion resistance plates. And smooth rotating doors are fitted on the incoming and outgoing terminals (please open the door from down to up and close or open the door on the side from up to down). While opening the door, the incoming and outgoing line units and operating units of RMU can be seen. The incoming and outgoing line units are connected with cable connectors and bushings, and the bushing are fixed under the operating panel, which makes it easy to connect with cable. The operating mechanism is fixed in the front of the face plates in order to make the motor-drive operation easy. The main components inside the RMU Switchgear are vacuum load switch and Vacuum Circuit Breaker, which can control and protect the incoming line and the outgoing line. The user can choose the combined mode according to what they need. The typical scheme is two outgoing lines and two incoming lines (composed of four main switches). At the same time, the Current Transformer, Voltage Transformer and lightning arrestor and other elements are able to be fitted.

B. Another structure is that the outdoor RMU is fitted in imported SF6 RMU, product feature is:
It is feature by compact structure, small size, less occupied area and fine looking. The body is made of compound plates and the ceiling is made of glazed tile. There is a RMU imported from Germany, the origin place, which has the characteristics of seal, insulation, high reliability and being free of maintaining. The internal malfunction electric arc restraint device is fitted in the RMU, which can provide the greatest level of protection for personnel and equipments. It is easy to alternate the fuse for the SF6 RMU. When the fuse melts, it sends mechanical indication signal. The fuse'dimension is complied with IEC Standards and it has remote control joints, interlock of Earthing Switch. The function of mechanical interlock is complete, simple but reliable (complied with "Five protection"requirement) and can prevent varieties of incorrect manipulation, besides it is in conformity with GB3906-1991 and GB11022-1999 requirement. The dimension requested in the scheme of "two incoming line and one outgoing line"scheme, 1400*900*1630( width*depth*height).
No. Name Unit Parameter
1 Rated voltage kV 12
2 Rated frequency Hz 50
3 Rated current
 
A 630
4 Rated short-time withstand current kA 25
5 Power frequency withstand voltage kV 42
6 Lightning impulse withstand voltage kV 95
7 Environmental temperature º C -25 TO +60
8 Protection level   IP44

b.
Technical parameter table of vacuum circuit breaker and outdoor RMU of vacuum load switch manufactured by our company:
Name Unit Parameter
Rated voltage kV 12
Rated frequency Hz 50
Rated current of main busbar A 630
Rated current
(functional units)
A 630/200
3s rated short-time withstand current
(r. m. s of functional units)
kA 20
Rated short circuit breaking current
(outgoing line terminal)
kA 20
Rated short circuit making current kA 50
Rated peak withstand current (peak value) kA 50
Rated active load breaking current A 630
Rated closed loop breaking current A 630
5% rated active load breaking current A 31.5
Rated cable charging breaking current A 10
Rated no load transformer breaking capacity kVA 1600
1min power frequency withstand voltage
of main circuit   dry state/ hygrometric state
(phase to phase, phase to earth, between
isolating distance) (r. m. s )
kV 42/38
Lightning impulse withstand voltage   phase to earth, phase to phase  and isolating distance     kV     75
1min power frequency withstand voltage of
secondary circuit (r. m. s)
  kV       2

Contact us if you need more details on Zhw2-12 Outdoor AC Metal-Clad Switchgear. We are ready to answer your questions on packaging, logistics, certification or any other aspects about Power Distribution and Transformation、Power Equipment. If these products fail to match your need, please contact us and we would like to provide relevant information.

Product Categories : HV Switchgear