Find Current Transformers, Electronic Transformers, Oil Immersed Distribution Transformer on Industry Directory, Reliable Manufacturer/Supplier/Factory from China.

Inquiry Basket (0)
Home > Products > Power Transformer > Oil Immersed Distribution Transformer > Buried Underground Distribution Transformer (S11-MD)

Buried Underground Distribution Transformer (S11-MD)

Basic Info

Model No.:  S11-MD

Product Description



Model NO.: S11-MD


Phase: Three


Cooling Method: Oil-immersed Type Transformer


Certification: ISO9001-2000, ISO9001


Frequency Characteristics: High Frequency


Brand: Ville


Specification: IEC CE, ISO


HS Code: 8504231100




Application: Power, Electronic, Instrument, Lighting, Rectifier, Audio


Core: Core-type Transformer


Winding Type: Two-winding Transformer


Usage: Distribution Transformer


Shape of Core: Ring


Trademark: VILLE


Origin: Ningbo China


Buried Distribution Transformer

Features: S11-MD-underground distribution transformer core cold-rolled silicon steel miter joints using low-loss step-stack from the system. High and low voltage coil using cylindrical and spiral wound structure. Transformer low voltage side of the watertight box structure using high-pressure side of the head with waterproof cable products with anti-pollution, water and strong, no-load current, low noise, low loss, low temperature characteristics, the product can be charged continuously run for a certain time soaking advantages. Advanced technical indicators, unique structure, exquisite appearance, is particularly suitable for a water environment such as underground tunnels of a high-tech, high-performance energy-saving products.



The transformers can be buried underground in pits ,and can meet the needs of single ring high -voltage Power Supply,applies to long distances but small loading system ,such as roads ,bridges,and tunnels.



35KV Oil-Immersed Distribution

20kV(11KV) SZ11 Series three phases low lose oil-immersed on-load regulation distribution transformer(copper winding)

Introduction

1.3Ph,HV:(6,6.3,10.5,11,15KV ) LV:(0.415,0.4,0.69 KV)

2,Rated Capacity:10kVA~20MVA



Transformer Standard

GB 1094.3-2003( IEC 60076-3-2000)



Service Condition

1, 1) Altitude: ≤1, 000m

2) Maximal ambient temperature: +40.C

3) Maximal daily average temperature: +30.C

4) Maximal annual average temperature: +20.C

5) Minimal ambient temperature: -25.C

6) Indoor or outdoor








Tech data of 10kV SZ11 series on-load regulation distribution transformer
Rated capacity(KVA) Voltage group(kV) Vector group Impedance voltage(%) Loss(kW) No-load current (%) Weight(kg) Outline dimension (mm) Gauge vertical/Horizontal
No-loss Load Body Oil Total
200 (HV) 6-15kV (LV) 0.415-6kV Yyno Dyn11 4 0.34 3.06 1.5 540 270 1110 1400*740*1190 550/550
250 0.4 3.6 1.4 640 290 1270 1420*790*1210 660/660
315 0.48 4.32 1.4 730 320 1500 1540*850*1240 660/660
400 0.57 5.22 1.3 940 370 1780 1590*940*1250 660/660
500 0.68 6.21 1.3 1040 370 1920 1650*1000*1350 660/660
630 4.5 0.81 7.65 1.1 1220 460 2280 1810*1140*1350 820/820
800 0.96 9.36 1 1500 500 2740 1890*1200*1310 820/820
1000 1.15 10.98 1 1610 520 3060 1910*1260*1570 820/820
1250 1.36 13.05 0.9 1880 700 3710 1960*1280*1740 820/820
1600 1.64 15.57 0.8 2290 780 4350 2330*1800*1910 820/820
2000 1.96 21.26 0.8 2560 900 4950 2580*1900*1950 820/820
2500 2.31 24.69 0.7 3170 1010 6020 2580*1940*2250 1070/1070
Note:it can supply voltage regulating range of ±4*2.5%for HV on load regulation transformers



Contact us if you need more details on Transformer. We are ready to answer your questions on packaging, logistics, certification or any other aspects about Power Supply TransformerAuto Transformer. If these products fail to match your need, please contact us and we would like to provide relevant information.

Product Categories : Power Transformer > Oil Immersed Distribution Transformer