Model No.:  drum type/ tube type

Product Description

Model NO.: drum type/ tube type Phase: Three Cooling Method: Oil-immersed Type Transformer Application 1: Large or Medium Oil-Immersed Power Transformer Application 3: Transformers for Specially Used Suitable Oil Tank Type: Flat Type or Bell-Type Applied Oil Tank Rated Current: up to 2000A and Below Structure: Reliable Equipped with Solid Construct Trademark: VILLE HS Code: 85 Application: Power, Electronic, Instrument Core: Core-type Transformer Winding Type: Two-winding Transformer Application 2: Full Hermetically Transformer Applied Tranformer Frequency: Normally on 50 Hz or 60 Hz Applied Oil Tank Rated Voltage: up to 220kv and Below Appearance: Simple and Lively Performance: Light Moment, Turn Over Tap Position Clearly Origin: Ningbo Introduction

This is an new three-phase tube-type tap changer. It is combined by the body of tap changer and an operating turning framework, when the transformer is under non-energized state, we can turn over the tap position to change transformer ratio and stabilize output voltage. This single phase and "1+2" phase tube-type tap changer are suitable for installation on vertical direction, but the three-phase tube-type product is suitable for vertical or horizontal installation.

Application
These series of products are specially designed for large or medium oil-immersed power transformer, full hermetically transformer or transformers for specially used, they are frequency normally on 50 Hz or 60 Hz, and suitable for flat type or bell-type oil tank, its rated voltage is up to 220kV and below, rated current up to 2000A and below.

Technical Features
1) Simple and lively appearance, reliable structure equipped with solid construct pieces.
2) Light moment, turn over tap position clearly.
3) Design features: Body pieces are restricted each other and functioned each other. You can change the tap position freely and exactly, compared with the same type of products, it has obvious superiority.
4) No conductors and switch cover being equipped on the outer body of product. This is a full hermetically outer insulation screen which can withstand high voltage impulse, so no puncture discharge will rise between the narrow gaps, even if the air gap of the tap changer is very near the achieve body of the transformer.
5) The inner constructure of the tube-- type tap changer can be drawn out as a whole part, this helps to installation and maintenance.
6) It owned a certain of national patents right protection.

Main performance  parameter Insulation Leve (kV) Sealing performance (Pa/24h) Machine Life(Ten thousand times) Rated through current (A) Heat Stableness current (kA/2s) Dynamic stableness current (kA)
Line-frequency ( 1 min ) ( 1.2/50 μs)
Voltage class (Kv) Wiring mode To ground Inter phase Inter contactor To ground Interphase Intercontactor
10 Y 48 48 48 150 115 85 6×10 4 2 250 5 12.5
400 6 15
Delta 48 48 18 150 150 85 500 7.5 13.75
35 Y 100 48 30 230 150 95 630 9.45 23.6
Delta 100 100 30 230 230 95 800 9.73 24.3
66 Y 160 100 30 350 230 160 1000 10 25
Delta 160 160 45 350 350 150 1250 12.5 31.25
110 Y 230 160 45 480 350 150 1600 16 40
Delta 230 230 55 480 480 175 2000 20 50
220
460 *260/400 90 1100 1100 285 2500 25 62.5
3000 30 75

Contact us if you need more details on Tap Changer. We are ready to answer your questions on packaging, logistics, certification or any other aspects about Off-Circuit Tap Changer、Power Transformer Part. If these products fail to match your need, please contact us and we would like to provide relevant information.